Add to Cart
With Level Detector Oil Tester 11kw 600L/H Vacuum Transformer Oil Purifier
The Reason of Contamination:
1. Transformer oil under the action of thermoelectric field, oil and oxygen contact is gradually oxidized into various oxides and acids, alcohols and other forms of insoluble gum.
2. Due to the leakage of the system, the seal is not strict, the oil is in heat load for a long time, and the open oil storage and other reasons, the water and gas in the air settle in the oil, resulting in water and gas in the oil.
Vacuum Transformer Oil Purifier Description:
-VF series transformer oil purifier is a dehydration and degassing unit with thermal and vacuum processing. Comparing with Sino-NSH-VFD, this series is more suitable for smaller oil quantity or smaller capacity requests.
-VF series transformer oil purifier is mainly used to improve the properties of insulating oils in electric power transformers and other oil filled electrical equipment. It can remove dissolved and free water, dissolved gas and particulate impuritie effectively so as to increase special indexes of insulation oil.
-VF series transformer oil purifier combines vacuum flashing evaporation technology and delaminating gradual-close filter technology to reach best performance of oil purification. Meanwhile, by integrating efficient thermal and double-stage vacuum, the breakdown voltage is highly improved, which can be increased from 25kV to over 60kV.
Vacuum Transformer Oil Purifier Technical Parameters:
Parameter | Value | |||||
VF-10 | VF-20 | VF-30 | VF-50 | VF-100 | ||
Capacity, liters/hour | 600 | 1200 | 1800 | 3000 | 6000 | |
Heating Power, kW | 9 | 15 | 24 | 36 | 60 | |
Total Power, kW | 11 | 17 | 26 | 39 | 65 | |
Power supply | Fully Customizable | |||||
Inlet Diameter, mm | 25 | 25 | 25 | 32 | 40 | |
Outlet Diameter, mm | 25 | 25 | 25 | 32 | 40 | |
Dimensions (without trailer) | length, mm | 1300 | 1400 | 1400 | 1400 | 1550 |
width, mm | 900 | 900 | 900 | 900 | 1550 | |
height, mm | 1300 | 1300 | 1300 | 1700 | 1850 | |
Weight(without trailer), kg | 300 | 330 | 350 | 400 | 650 | |
Processed Oil Spec | Water Content, ppm | ≤7 | ||||
Dielectric Strength, Kv | ≥60 | |||||
Filtration Fineness, um | ≤5( or 1-5 as needed ) | |||||
Gas Content, % | ≤0.1 |
Working Principle:
1.Vacuum oil purifier is designed according to the boiling point of water and oil. It is composed of vacuum heating tank, fine filter, primary filter, vacuum pump, exhaust oil pump and electrical cabinet.
2. Vacuum pump will air out creating vacuum in the vacuum tank, the oil under the action of atmospheric pressure, oil after entrance pipe into the prefilter to remove larger particles, and then enter the heating tank, after heated to a temperature of 40-75 ℃ of oil into the vacuum tank, oil in water evaporate into water vapor rapidly and continuously in the vacuum pump oil water separator, The water vapor in the separator is cooled and reduced to water before being released.
3. The oil in the vacuum heating tank is discharged into the fine filter by the exhaust pump through the filter element to filter out the particulate impurities. In order to complete the vacuum filter quickly remove impurities in the oil, water, gas, the whole process, so that the clean oil discharged from the exit of the machine.
Optional:
1. Single axle trailer,double axle trailer,trailer with enclosure doors
Rode-worthy, 2 pneumatic tyres or 4 pneumatic tyres, pre-leg, two-eye, brake, rear lights,etc
2. Separated operation room
With inspection window, air conditioning, operation desktop, storage sapce, etc, any custom option
3. Explosion-proof
Tailored according to usage, i.e: Exd II BT4 or Exd II CT4
4. Full automatic
PLC, touch screen/text screen/mimic diagram, data monitoring.
5. Steel enclosure shield
Weather-proof, steel cover, horizontal/vertical doors, hydraulic supports
6. Aluminum enclosure shield
Weather-proof, aluminum cover, horizontal/vertical doors, hydraulic supports
7. Station with forklifts hole type
Thicken chassis, forklifts hole, hoisting eyes on top, etc.
8. Tailored
Available in kinds requirements